Current Transformer Overview

VFD and SCR output waveforms are rough approximations of a sine wave. There are numerous spikes and dips in each cycle. ATR transducers use a mathematical algorithm called "True RMS," which integrates the actual waveform over time. The output is the amperage component of the true power (heating value) of the AC current waveform. True RMS is the only way to accurately measure distorted AC waveforms. Select ATR transducers for nonlinear loads or in "noisy" power environments.

The current waveform of a typical linear load is a pure sine wave. AT transducers measure the peaks of these sine waves, then calculate the average amperage. This works well on constant speed linear loads in a "clean" power environment. Select AT transducers for strictly linear loads on "clean" power.

ATR 0, 1 & 2 0-2 to 0-200A AC True RMS Download data sheet (pdf) file size: 934 Kb
AT 0, 1 & 2 0-2 to 0-200A AC Average sensing Download data sheet (pdf) file size: 502 Kb
AT/ATR 3 & 4 0-375 to 0-2000A AC High Current Download data sheet (pdf) file size: 467 Kb
ATP 0, 1 & 2 0-2 to 0-200A AC Powered Transducer Download data sheet (pdf) file size: 878 Kb
AP/APR 0, 1, 2, & 3 0-10 to 0-400A AC DIN-rail Current Transducer Download data sheet (pdf) file size: 1.4 Mb
ATQ 0, 1 & 2 0-2 to 0-200A AC Frequency Output Download data sheet (pdf) file size: 452 Kb
DT 1, 2, 3 & 4 0-50 to 0-400A DC Hall effect technology Download data sheet (pdf) file size: 509 Kb

 

 
 

ATR Series

Larger version - 20K - Click

‘ATR’ transducers from NK Technologies combine a current transformer and a True RMS signal conditioner into a single package. The ATR Series provides True RMS output on distorted waveforms found on VFD or SCR outputs and on linear loads in "noisy" power environments. Available in a solid or split core case.

Applications

  • VFD Controlled Loads
    VFD output indicates how the motor and attached load are operating.
  • SCR Controlled Loads
    Accurate measurement of phase angle fired or burst fired (time proportioned) SCRs. Current measurement gives faster response than temperature measurement.
  • Switching Power Supplies and Electronic Ballasts
    True RMS sensing is the most accurate way to measure power supply or ballast input power.

Larger version - 15K - Click Features

  • True RMS Output
    True RMS technology is accurate on distorted waveforms like VFD or SCR outputs.
  • Jumper Selectable Ranges
    — Reduces inventory.
    — Eliminates zero and span pots.
  • Isolation
    — Output is magnetically isolated from the input for safety.
    — Eliminates insertion loss (voltage drop).
  • UL, CUL and CE Approval
    Accepted worldwide.

Specifications

Output Signal 4–20mA, Loop-powered, True RMS
Output Limit 23mA
Accuracy 0.8% FS
Response Time 600mS (to 90% step change)
Frequency Range 10–400Hz
Power Supply 24VDC Nominal, 40VDC Maximum
Isolation Voltage UL listed to 1,270VAC, tested to 5KV
Input Ranges Field selectable from 0–200A (see Ordering Information). Consult factory for custom ranges.
Sensing Aperture • FT Models: 0.75" (19mm) dia.
• SP Models: 0.85" (21.5mm) sq.
Case UL 94V-0 Flammability rated
Environmental –4 to 122°F (–20 to 50°C), 0–95% RH, non-condensing
Listings UL 508 Industrial Control Equipment (USA & Canada), CE (Pending)

 

 

 

AT Series

‘AT’ Current Transducers from NK Technologies combine a current transformer and signal conditioner into a single package. The AT Series has jumper selected current input ranges and industry standard 4–20mA, 0–5VDC or 0-10VDC outputs. The AT Series is designed for application on ‘linear’ or sinusoidal AC loads. Available in a split core case or two types of solid core cases.

Larger version - 11K - Click Applications

  • Automation Systems
    Analog current reading for remote monitoring and software alarms.
  • Data Loggers
    Self-powered transducer does not drain data logger batteries.
  • Panel Meters
    Simple connection displays power consumption.

Features

  • Accurate
    Factory matched and calibrated single piece transducer is more accurate than traditional two-piece field installed solutions.
  • Average Responding
    "Average responding" algorithm gives a RMS output on pure sine waves. Perfect for constant speed (linear) loads.
  • Jumper Selectable Ranges
    — Reduces inventory.
    — Eliminates zero and span pots.
  • Isolation
    — Output is magnetically isolated from the input for safety.
    — Eliminates insertion loss (voltage drop).
  • UL, CUL and CE Approval
    Accepted worldwide.

     

Specifications

  –005 Models –010 Models –420 Models
Output Signal 0–5VDC 0–10VDC 4–20mA
Output Limit 10VDC 15VDC 40mA
Accuracy 1.0% FS 1.0% FS 0.5% FS
Response Time
(10–90% step change)
100mS 100mS 300mS
Frequency Range 50–60Hz 50–60Hz 20–100Hz*
Other Frequencies Special calibration available for any frequency from 10–400Hz*
Power Supply Self-powered Self-powered 12–40VDC,
Loop-powered
Loading 1m W minimum for rated accuracy
100K W add 1.3% error
See "Power Supply" below
Isolation Voltage UL listed to 1,270VAC, tested to 5KV
Input Ranges Field Selectable Ranges from 0–200A (see Ordering Information). Custom ranges available, consult factory.
Sensing Aperture • FF Case: 0.55" (14mm) dia.
• FT Case: 0.75" (19mm) dia.
• SP Case: 0.85" (21.5mm) sq.
Case UL 94V-0 flammability rated
Environmental –4 to 122°F (–20 to 50°C), 0–95% RH, non-condensing
Listings UL 508 Industrial Control Equipment (USA & Canada), CE

*For sinusoidal waveforms only. Select ATR Transducers for distorted waveforms

 

AT/ATR 3 & 4 Series

'AT/ATR 3 & 4' transducers from NK Technologies combine a high capacity current transformer and a signal conditioner into a single package. The AT version is Average Responding for use on linear (sinusoidal) loads. The ATR version is True RMS for use on distorted waveforms found in VFD or SCR outputs. Available in a solid or split core case. 

Applications

  • Large Pumps
    Detect dry run electronically.
  • Generation
    Measure the output of generators.
  • Electric Heating Elements
    — Monitors heater load.
    — Faster response than temperature sensors.

Features

  • Large Aperture
    Accommodates large conductors or wire bundles.
  • Select the Right Output
    — True RMS technology is accurate on distorted waveforms like VFD or SCR outputs.
    — Average Responding-for linear, sinusoidal waveforms
  • Three Jumper Selectable Ranges
    — Reduces inventory.
    — Eliminates zero and span pots.
  • Isolation
    Magnetic isolation protects installers and systems.
  • Easy Installation
    Single piece with integral mounting brackets makes for a simple, solid installation.
  • UL, CUL and CE Approval
    Accepted worldwide.

 

Specifications

Output Signal 4-20mA, Loop-powered
Output Limit 23mA
Accuracy 1.0% FS accuracy, True RMS
Measurement True RMS or Average Responding (see Ordering Information)
Response Time 500mS (to 90% of step change)
Frequency Range • ATR: 10-400Hz
• AT: 50-60Hz, Sinusoidal
Power Supply 24VDC Nominal; 40VDC Maximum
Isolation Voltage 600VAC
Input Ranges • AT/ATR3: 375, 500, 750A
• AT/ATR4: 1000, 1333, 2000A
Sensing Aperture 3.0" (76mm) dia.
Case UL 94 Flammability rated
Environmental -4 to 122°F (-20 to 50°C), 0-95% RH, non-condensing
Listings UL 508 Industrial Control Equipment (USA & Canada), CE (Pending)

 

 

DT Series

'DT' Current Transducers from NK Technologies combine a Hall effect sensor and signal conditioner into a single package. The DT Series has jumper selectable current input ranges and industry standard 0-20mA, 4-20mA, 0-3VDC, 0-5VDC or 0-10VDC outputs. Available in a split core package.

Larger version - 16K - Click Applications

  • Battery Banks
    — Monitors load current.
    — Monitors charging current.
    — Verifies operation.
  • Transportation
    Measures traction power or auxiliary loads.
  • Electric Heating Elements
    Faster response than temperature sensors.

Features

  • Three Jumper Selectable Ranges
    — Reduces inventory.
    — Eliminates zero and span pots.
  • Isolation
    — Output is magnetically isolated from the input for safety.
    — Eliminates insertion loss (voltage drop).
  • Internal Power Regulation
    — Works well, even with unregulated power.
    — Cuts installation costs.
  • Easy Installation
    Split core design with built-in mounting brackets makes installation a snap.

 

Specifications

Output Signal 0-20mA, 4-20mA, 0-3VDC, 0-5VDC or 0-10VDC
Output Limit • 0–20mA, 4–20mA: 44mA
• 0–3VDC: 6.5VDC
• 0–5VDC: 13VDC
• 0–10VDC: 26VDC
Accuracy 1.0% FS
Repeatability 1.0% FS
Response Time 100mS (to 90% of step change)
Frequency Range DC
Power Supply 20–50VDC, 22–38VAC. Power input and output signal are not isolated.
Power Consumption 2VA
Loading • 0–20mA, 4–20mA: 650 max.
• 0–3/5/10VDC: 250k for rated accuracy; 25k, add 1% error.
Isolation Voltage 3kV (monitored line to output)
Linearity 0.75% FS
Current Ranges Field Selectable Ranges from 0–400A (see Ordering Information)
Sensing Aperture 0.85" (21.5mm) sq.
Case UL 94V-0 Flammability rated
Environmental –4 to 122°F (–20 to 50°C), 0–95% RH, non-condensing

 

 

Current transformers


Larger version - 14K - Click Traditional 5 Amp plus "ProtectCT" for simple, fast and safe installation. Split-core and solid-core.
 

Current Transformers: Split Core Models

CTP-075 5-150A 0.75" square aperture 0.333VDC O/P Download data sheet (pdf) file size: 46 Kb
CTP-125 100-600A 1.25" square aperture 0.333VDC O/P
CTP200 600-1500A 2.0" square aperture 0.333VDC O/P
500 300-1500:5 4.1"x7.1" ID 5Amp Download data sheet (pdf) file size: 307 Kb
600 400-2000:5 2.0"x5.5" ID 5Amp Download data sheet (pdf) file size: 253 Kb
601 400-2000:5 4.5"x5.5" ID 5Amp
604 100-400:5 1.4"x1.5" ID 5Amp Download data sheet (pdf) file size: 263 Kb
606 200-1200:5 2.6"x2.75" ID 5Amp Download data sheet (pdf) file size: 289 Kb
608 500-3200:5 2.6"x6.25" ID 5Amp
613 100-400:5 0.8"x1.9" 5Amp Download data sheet (pdf) file size: 239 Kb

Download all Split-Core data sheets (zip) (sit) - files size 1,398 kb • 1,427 kb

 


Solid Core Models

2RL/SFT 50-300:5 1-1/8" ID 5Amp Download data sheet (pdf) file size: 186 Kb
5RL/SFT 50-1200:5 1-1/2" ID 5Amp Download data sheet (pdf) file size: 201 Kb
7RL/SFT 50-1600:5 2-1/2" ID 5Amp Download data sheet (pdf) file size: 195 Kb
8RL/SFT 200-4000:5 3-1/4" ID 5Amp Download data sheet (pdf) file size: 262 Kb
170RL/SFT 200-4000:5 4-1/4" ID 5Amp Download data sheet (pdf) file size: 194 Kb
125RL/SFT 600-4000:5 6-1/4" ID 5Amp Download data sheet (pdf) file size: 164 Kb
126RL/SFT 400-5000:5 8-1/4" ID 5Amp Download data sheet (pdf) file size: 168 Kb

 


3 Phase Models

3P3 50-300:5 0.97" ID (3) 5Amp Download data sheet (pdf) file size: 190 Kb
3P4 50-1000:5 1.44" ID (3) 5Amp Download data sheet (pdf) file size: 137 Kb
3P18 50-400:5 1.19" ID (3) 5Amp Download data sheet (pdf) file size: 161 Kb
3P30 200-2000:5 2.88" ID (3) 5Amp Download data sheet (pdf) file size: 208 Kb