AG Series sensors from NK Technologies
protect people, products and processes from ground
faults by monitoring all current-carrying wires in grounded single or
3-phase systems.
Operating Principle: Under
normal conditions, the current in the hot leg of a two-wire load is
equal in strength but opposite in sign to the current in the neutral
leg. These two currents create magnetic fields that are also equal but
opposite. When the wires are next to each other, the fields cancel,
producing a "Zero Sum Current". If any current leaks to ground from
one wire (Ground Fault), the two currents become imbalanced and the
result is a net magnetic flux or field. AG Series ground fault sensors
monitor this field and alarm when leakage rises above setpoint. This
concept applies to grounded 3-phase delta and wye systems.
- Operation to Match Your Application:
Latching For controlling
contactors. Auto-Reset
For controlling shunt trip breakers.
- Setpoint Options to Match Your Needs:
Tri-Set Field select 5, 10
or 30mA. Fast and convenient. (AG3 only)
Single-Set Factory adjusted setpoint.
Specify 5100mA (AG1) or 80950mA (AG2) when ordering.
- Compatible with Standard Equipment
Works on 1F or 3F
power. Controls standard shunt trip breakers or contactors. Tie into
Emergency Circuits (EMO/EPO).
- Isolated
Magnetically isolated from the monitored
circuit and control power
- UL and CE Approval
Accepted worldwide.
- Personnel Protection
(typically 5mA)
Senses low fault currents and alarms to shut power
before injury occurs.
- Equipment Protection
(typically 30mA)
When personal protection is not an issue, select a higher setpoint
to protect equipment or product.
- Regulatory Approval
Meet requirements by industry groups and
governments for Ground Fault Protection.
| Setpoint Range |
|
"Single-Set" Models
|
Factory adjusted and sealed (field adjustment
possible) |
| AG1: 5100mA, specify when ordering |
| AG2: 80950mA, specify when ordering |
|
"Tri-Set" Models
|
5, 10 & 30mA jumper select |
| Output |
Isolated dry contact (solid state or relay,
see Ordering Information) |
| Output Rating |
Solid State AC Switch: 1A @ 240VAC
Solid State DC Switch: 0.15A 30VDC
Relay: 0.5A @ 125VAC, 2A @VDC |
| Off State Leakage |
None |
| Response Time |
200mS @ 5% above setpoint
60mS @ 50% above setpoint
15mS @ 500% above setpoint |
| Isolation Voltage |
Up to 1,250VAC (monitored circuit) |
| Frequency Range |
50400Hz (monitored circuit) |
| Sensing Aperture |
0.75" (19mm) dia., up to 4" (100mm) dia.
available, consult factory. |
| Power Supply |
120, 200, 208, 220, 240VAC, 50-400Hz,
operates from 55110% of nominal voltage
24VAC & 24VDC, operates +/10%
Green LED = power (all models) |
| Case |
UL 94V-O Flammability rated |
| Environmental |
5 to 158°F (15 to 70°C), 0-95% RH,
non-condensing |
| Safety |
UL 1053, Class 1 Recognized, CE* |
*Most option combinations are UL recognized.
| Normally Energized Models (FS
Option) |
|
|
Control Power
Applied |
| No Power |
No Fault |
Fault |
| N.C. Normally Closed |
Closed |
OPEN |
Closed |
| N.O. Normally Open |
Open |
CLOSED |
Open |
| Normally Deenergized Models (NF
Option) |
|
|
Control Power
Applied |
| No Power |
No Fault |
Fault |
| N.C. Normally Closed |
Closed |
CLOSED |
Open |
| N.O. Normally Open |
Open |
OPEN |
Closed |
| Latching (LA Option) |
Latching models initially power up in the
Reset position. If there is a fault or the test button is
pressed, the output switches and is latched. The output will
remain latched after the fault is cleared, even if control power
is removed. To reset the output, apply a momentary contact
across the "Reset" terminals (67).
|
|