|
Yaskawa / Magnetek AC Inverters and AC
Vector Drives |
|
1/2 - 500 Horsepower Industrial Workhorse
|
|

|
Specifications and Features for F7 Drive
|
The F7 Drive: This AC drive is the Industrial Workhorse that can
handle every conventional application found within the typical
industrial plant, from simple variable torque pumping to
sophisticated networked material handling. All of this is possible
with the smart and flexible design platform of the F7, providing
both Normal and Heavy Duty ratings, four modes of control, network
communication options, application-specific drive software, and an
array of standard and optional input/output choices.
The F7 is factory-programmed and ready to run. For operational
simplicity and clarity, the LCD operator display has 5 lines x 16
characters. It can be set to any of 7 languages. The keypad is
intuitive and includes parameter copying to move a chosen set of
parameters from one drive to another. If the application requires
programming, the F7 makes it easy. Parameters are grouped in easy to
use sets; quick start and advanced. To enhance parameter and data
management, DriveWizard software for the PC is available at no
charge, for upload/download, trending, and graphing.
This drive is designed for tough industrial environments. It is
rugged and reliable, with an MTBF of 28 years. A variety of
enclosure options provide the right environmental protection. The
dual ratings, Normal and Heavy duty, enable the most economical
match of overload capacity and starting torque for the application.
Providing the right fit to power requirements is also easy with
208/240 and 480 volt ratings, built-in bus choke above 30 HP,
12-pulse capability above 30 HP, common bus capability, and
regeneration options. Patented high slip braking can eliminate the
need for dynamic braking resistors for high inertia loads. Other
features include motor auto-tuning and a wide range of configurable
options, such as breakers and fuses.
To provide the optimum control method, the F7 can operate in
conventional V/f, V/f with encoder feedback, open loop vector, or
closed loop vector mode. Drive performance can be further enhanced
for a specific application with optional software.
The F7 supports the industry’s open architecture, open connectivity
demands with network communications choices such as DeviceNet,
Profibus-DP, and others. Drive coordination with other equipment is
simplified with inputs and outputs for digital pulse train, 4 to 20
mA, -10 to +10 V, and an assortment of programmable contacts.
For new installations or retrofits, the F7 is truly the Industrial
Workhorse, perfect for every conventional application…and even some
unconventional ones
|
Documentation |
|
|
|
|
Rev Date |
Size |
|
EZZ006543 |
Making Yaskawa Inverter Products Conform with the
EMC Directive |
Technical Manuals |
4/4/2002 |
353 KB |
|
IG.AFD.12 |
Installation Guide for Profibus DP Option CM061 |
Installation Guides |
7/1/2004 |
1.1 MB |
|
IG.AFD.13 |
Installation Guide for DeviceNet Option Card CM059
|
Installation Guides |
7/1/2004 |
124 KB |
|
IG.AFD.14 |
Installation Guide for DeviceNet Option Card CM05X
|
Installation Guides |
7/1/2004 |
109 KB |
|
IG.AFD.17 |
Installation Guide for Modbus Plus Option Card CM071
|
Installation Guides |
7/1/2004 |
1.8 MB |
|
IG.AFD.20 |
Installation Guide for LonWorks Option |
Installation Guides |
7/1/2004 |
94 KB |
|
IG.AFD.25 |
Installation Guide for EthernetModbusTCP/IP Option
CM090 |
Installation Guides |
7/1/2004 |
121 KB |
|
IG.AFD.50 |
Installation Guide for Pressure Transducer 3-15 PSI
Analog Input Option Card AI-010 |
Installation Guides |
7/1/2004 |
147 KB |
|
IG.AFD.51 |
Installation Guide for Analog Ouput Option Card
AO-08 AO-12 |
Installation Guides |
7/1/2004 |
63 KB |
|
IG.AFD.52 |
Installation Guide for Isolated Analog Output Option
Card AO-001 |
Installation Guides |
11/3/2004 |
89 KB |
|
IG.AFD.53 |
Installation Guide for Analog Input Option Card
AI-14U |
Installation Guides |
7/1/2004 |
44 KB |
|
IG.AFD.54 |
Installation Guide for Analog Input Option Card
AI-14B |
Installation Guides |
7/1/2004 |
81 KB |
|
IG.AFD.55 |
Installation Guide for Isolated Analog Input Option
Card AI-040 |
Installation Guides |
7/1/2004 |
80 KB |
|
IG.AFD.56 |
Installation Guide for Digital Output Option Card
DO-08 |
Installation Guides |
7/1/2004 |
108 KB |
|
IG.AFD.57 |
Installation Guide for Digital Output Option Card
DO-02C |
Installation Guides |
7/1/2004 |
113 KB |
|
IG.AFD.58 |
Installation Guide for Digital Input Option Card
DI-08 |
Installation Guides |
7/1/2004 |
49 KB |
|
IG.AFD.59 |
Installation Guide for Digital Input Option Card
DI-16H2 |
Installation Guides |
7/1/2004 |
68 KB |
|
IG.AFD.60 |
Installation Guide for Encoder Feedback Option Card
PG-X2 |
Installation Guides |
7/1/2004 |
114 KB |
|
IG.AFD.61 |
Installation Guide for Dual Encoder Feedback Option
Card PG-W2 |
Installation Guides |
7/1/2004 |
101 KB |
|
IG.AFD.62 |
Installation Guide for Analog Input Trim
Potentiometer Option Card AI-001 |
Installation Guides |
7/1/2004 |
31 KB |
|
IG.AFD.63 |
Installation Guide for 120 VAC Interface Option Card
DI-001 |
Installation Guides |
10/3/2004 |
63 KB |
|
IG.F7C.01 |
Installation Guide for Heatsink Filter Kit Option
for F7 Configured Drive |
Installation Guides |
3/5/2004 |
87 KB |
|
TM.AFD.12 |
Technical Manual for Profibus-DP Option CM052 |
Technical Manuals |
1/31/2004 |
2.4 MB |
|
TM.AFD.13 |
Technical Manual for DeviceNet Option CM059 |
Technical Manuals |
5/1/2004 |
929 KB |
|
TM.AFD.14 |
Technical Manual for DeviceNet Option CM05x |
Technical Manuals |
4/1/2004 |
523 KB |
|
TM.AFD.20 |
Technical Manual for LonWorks Option |
Technical Manuals |
3/30/2004 |
479 KB |
|
TM.DW.03 |
DriveWizard 6.0 Software User Manual |
Technical Manuals |
9/14/2004 |
1.6 MB |
|
TM.F7.01 |
F7 DRIVE USER MANUAL |
Technical Manuals |
10/15/2004 |
3.9 MB |
|
TM.F7.02 |
F7 Drive Programming Manual |
Technical Manuals |
11/1/2004 |
1.7 MB |
|
TM.F7.11 |
Technical Manual for F7 Parameter Access |
Technical Manuals |
2/1/2004 |
2.1 MB |
|
TM.F7SW.056 |
F7 Drive Software Technical Manual 1500 Hz Output
Frequency |
Technical Manuals |
7/1/2004 |
1.3 MB |
|
TM.F7SW.064 |
F7 Drive Software Technical Manual Electronic
Lineshaft |
Technical Manuals |
7/1/2004 |
1.4 MB |
|
TM.F7SW.076 |
F7 Drive Software Technical Manual Differential PID
for Gas Well |
Technical Manuals |
7/14/2004 |
49 KB |
|
YEA-TOE-S616-55.1 |
Instruction Manual Varispeed-F7 Spec A |
Technical Manuals |
3/1/2001 |
6.8 MB |
|
YEA-TOE-S616-55.3 |
Instruction Manual Varispeed-F7 Obsolete manual for
F7U |
Technical Manuals |
10/1/2001 |
6.2 MB |
|
|
1/2 - 500 Horsepower The Ultimate Drive
Solution

|
Specifications and Features for G7 Drive
|
This amazing AC drive is the ultimate performance solution with
increased speed and torque response to provide servo-like
performance from an induction motor. In addition, the
G7 drive includes the world’s first Inverter
architecture that eliminates or minimizes the installation problems
associated with IGBT switching on 480 volt systems and protects the
entire motor-drive system.
G7 drive performance makes it the ideal drive for high performance
speed, torque, or position control applications. Several control
modes are provided. In open loop vector mode, the latest flux
observer algorithms extend speed range and provide maximum starting
torque. In closed loop vector mode, 0.01% speed regulation and
1000:1 control range can be achieved. Zero-servo capability provides
position control at zero speed.
The G7 drive has the world’s first 480V 3-Level Inverter
architecture for total system protection. This patented 3-Level
architecture can eliminate peripheral components typically required
to solve installation problems sometimes encountered on 480 volt
systems. The G7 allows motor operation at very long cable lengths,
meeting NEMA MG1 Part 31, with peak voltage being 30% less than
conventional. With motor bearing current being typically 50% less
than standard inverters, the G7 provides four times the motor
bearing life. Audible motor noise on the 480 volt G7 drive is 5-10
dB (20%) less than the prior generation drive, even when operating
at half the carrier frequency. Common mode current is half that of
conventional drives. The G7 power section includes built-in bus
choke (most ratings), 12-pulse input capability (most ratings),
common DC bus capability, and regeneration options.
The G7 drive has three autotuning methods to optimize motor control,
including the new static autotuning which does not require load
decoupling nor motor rotation. The LCD operator displays 5 lines x
16 characters, in any of 7 languages. The keypad is intuitive and
includes memory for parameter settings, making it easy to transfer
settings from one drive to another. To further aid in parameter
management, DriveWizard™ software for the PC is available at no
charge, for upload, download, archiving, trending, and graphing.
The G7 drive has a large programming feature set to handle
sophisticated industrial applications. If the standard feature set
does not meet your specific requirement, the G7 can be programmed
using DriveWorksEZ™. This is a PC-based, object-oriented, graphical
icon programming tool that is friendly to the user. The drive
firmware can also be modified by custom or prewritten
application-specific modules such as
Motion Control
or Electronic Lineshaft.
The G7 drive supports the industry’s
preference for open network architecture and connectivity with
network choices such as DeviceNet, Profibus-DP, Ethernet, and
others.
The G7 is not intended for the simple, routine
AC drive application, it is for the challenges. The G7 drive offers
the ultimate performance, the best system protection, and the most
flexible configurations of any drive available.
|
|
|
|
|
Rev Date |
Size |
|
EZZ006543 |
Making Yaskawa Inverter Products Conform with the
EMC Directive |
Technical Manuals |
4/4/2002 |
353 KB |
|
IG.AFD.12 |
Installation Guide for Profibus DP Option CM061 |
Installation Guides |
7/1/2004 |
1.1 MB |
|
IG.AFD.13 |
Installation Guide for DeviceNet Option Card CM059
|
Installation Guides |
7/1/2004 |
124 KB |
|
IG.AFD.14 |
Installation Guide for DeviceNet Option Card CM05X
|
Installation Guides |
7/1/2004 |
109 KB |
|
IG.AFD.17 |
Installation Guide for Modbus Plus Option Card CM071
|
Installation Guides |
7/1/2004 |
1.8 MB |
|
IG.AFD.20 |
Installation Guide for LonWorks Option |
Installation Guides |
7/1/2004 |
94 KB |
|
IG.AFD.25 |
Installation Guide for EthernetModbusTCP/IP Option
CM090 |
Installation Guides |
7/1/2004 |
121 KB |
|
IG.AFD.50 |
Installation Guide for Pressure Transducer 3-15 PSI
Analog Input Option Card AI-010 |
Installation Guides |
7/1/2004 |
147 KB |
|
IG.AFD.51 |
Installation Guide for Analog Ouput Option Card
AO-08 AO-12 |
Installation Guides |
7/1/2004 |
63 KB |
|
IG.AFD.52 |
Installation Guide for Isolated Analog Output Option
Card AO-001 |
Installation Guides |
11/3/2004 |
89 KB |
|
IG.AFD.53 |
Installation Guide for Analog Input Option Card
AI-14U |
Installation Guides |
7/1/2004 |
44 KB |
|
IG.AFD.54 |
Installation Guide for Analog Input Option Card
AI-14B |
Installation Guides |
7/1/2004 |
81 KB |
|
IG.AFD.55 |
Installation Guide for Isolated Analog Input Option
Card AI-040 |
Installation Guides |
7/1/2004 |
80 KB |
|
IG.AFD.56 |
Installation Guide for Digital Output Option Card
DO-08 |
Installation Guides |
7/1/2004 |
108 KB |
|
IG.AFD.57 |
Installation Guide for Digital Output Option Card
DO-02C |
Installation Guides |
7/1/2004 |
113 KB |
|
IG.AFD.58 |
Installation Guide for Digital Input Option Card
DI-08 |
Installation Guides |
7/1/2004 |
49 KB |
|
IG.AFD.59 |
Installation Guide for Digital Input Option Card
DI-16H2 |
Installation Guides |
7/1/2004 |
68 KB |
|
IG.AFD.60 |
Installation Guide for Encoder Feedback Option Card
PG-X2 |
Installation Guides |
7/1/2004 |
114 KB |
|
IG.AFD.61 |
Installation Guide for Dual Encoder Feedback Option
Card PG-W2 |
Installation Guides |
7/1/2004 |
101 KB |
|
IG.AFD.62 |
Installation Guide for Analog Input Trim
Potentiometer Option Card AI-001 |
Installation Guides |
7/1/2004 |
31 KB |
|
IG.AFD.63 |
Installation Guide for 120 VAC Interface Option Card
DI-001 |
Installation Guides |
10/3/2004 |
63 KB |
|
IG.G7.68 |
Installation Guide for 120VAC Interface Option Card
DI-003 |
Installation Guides |
10/3/2004 |
118 KB |
|
TM.AFD.12 |
Technical Manual for Profibus-DP Option CM052 |
Technical Manuals |
1/31/2004 |
2.4 MB |
|
TM.AFD.13 |
Technical Manual for DeviceNet Option CM059 |
Technical Manuals |
5/1/2004 |
929 KB |
|
TM.AFD.14 |
Technical Manual for DeviceNet Option CM05x |
Technical Manuals |
4/1/2004 |
523 KB |
|
TM.AFD.20 |
Technical Manual for LonWorks Option |
Technical Manuals |
3/30/2004 |
479 KB |
|
TM.DW.03 |
DriveWizard 6.0 Software User Manual |
Technical Manuals |
9/14/2004 |
1.6 MB |
|
TM.G7.01 |
G7 DRIVE TECHNICAL MANUAL |
Technical Manuals |
9/1/2004 |
4.5 MB |
|
|
5 - 500 Horsepower Industrial Fan and Pump
Drive

|
Specifications and Features for P7 Drive
|
For industrial applications such as centrifugal fans and pumps, the
P7 drive is an ideal choice. The drive is provided in Normal Duty
ratings with 110% overload capability. V/f control mode, network
communication options, and an array of input/output options are
available.
The P7 is factory-programmed and ready to run. For operational
simplicity and clarity, the LCD operator display has 5 lines x 16
characters. It can be set to any of 7 languages. The keypad is
intuitive and includes parameter copying to move a chosen set of
parameters from one drive to another. If the application requires
programming, the P7 makes it easy. Parameters are grouped in easy to
use sets; quick start and advanced. To enhance parameter and data
management, DriveWizard software for the PC is available at no
charge, for upload/download, trending, and graphing.
This drive is designed for tough industrial environments. It is
rugged and reliable, with an MTBF of 28 years. A variety of
enclosure options provide the right environmental protection.
Providing the right power requirements is also easy with 208/240 and
480 volt ratings, built-in bus choke above 30 HP, common bus
capability, and other energy savings options. Other features include
motor auto-tuning and configurable options such as circuit breakers
and fuses.
The P7 supports the industry's open architecture, open connectivity
demands with network communications choices such as DeviceNet,
Profibus-DP, and others. Drive coordination with other equipment is
simplified with inputs and outputs for 4 to 20 mA, 0-10 V, and an
assortment of programmable contacts.
With an optional phase-shifting input transformer, the P7 dual-diode
bridge can be operated in 12-pulse rectification mode, reducing
input current harmonic distortion factor by over 90%. With lower
EMI/RFI emission and lower total harmonic distortion contribution,
the P7 meets or exceeds the generally accepted power quality
standards. Inherent motor protection features resulting from low
noise/low carrier technology provides for longer lead lengths
without additional motor protection devices.
The optional P7/Bypass package is a 3-contactor style bypass,
allowing motor operation from the drive or across the line. This
facilitates drive maintenance while the motor continues to operate.
The P7 has been designed to provide the features and options
commonly needed for fan and pump applications.
Performance Features
- Ratings:
5-150 HP, 208 VAC
5-150 HP, 230 / 240 VAC
5-500 HP, 480 VAC
5-250 HP, Bypass
- Overload capacity: nominal 110% for 60 sec
(150% peak)
- Starting torque: 100% at 3 Hz
- DC injection braking: at start or stop,
adjustable,
- current-limited (anti-windmilling)
- Motor preheat function
- Adjustable accel/decel: 0.1 to 6000 sec.
- Controlled speed range: 40:1
- Critical frequency rejection: 3
selectable, adjustable bands
- Torque-limiting: 30-180%
- Energy $aving control
- Torque boost: full range, auto
- Power loss ride-thru: 2 sec
- Inertia ride-thru
- Auto restart after power loss or
resettable fault, selectable,
- programmable
- Feedback signal loss detection
- Serial communications loss detection
- "Up/Down" floating point control
capability
- Stationary motor auto-tuning
- Sleep function
- Run-permissive input
Protective Features
- Current-limited stall prevention
- Heat sink over-temperature, speed
fold-back
- Bi-directional start into rotating motor
- Current-limiting DC bus fuse
- Optically-Isolated controls
- Short circuit protection: Phase-phase and
phase-neutral
- Ground fault protection
- Short circuit withstand rating: 65K RMS,
100K RMS with bus reactor
- Electronic motor overload: UL
- Current limit
- Fault display: last 10 faults
- Fault circuit: OC, OV, OT
- Over torque and under torque protection
- Reverse prohibit selectability
Inputs and Outputs
- Output contacts: One form C and two
programmable form A
- Input terminals: 5 programmable
multi-function input terminals
- Fault input: Programmable
- Remote speed command: 0-10 VDC or 4-20 mA,
direct or reverse-acting
- Analog outputs: Programmable, two, 0-10
VDC
|
Design Features
- LCD keypad display, 5 lines x 16
characters, backlit, 7 languages,
- copy function
- Multi-step speed settings: 5 available
- Setpoint (PI) control
- 32-bit microprocessor logic
- Nonvolatile memory, program retention
- Displacement power factor: 0.98
- Output frequency: 0.1 to 120 Hz
- Frequency resolution: 0.06 Hz
- Frequency regulation: 0.1%
- Control Terminal Board: Quick disconnect
- Carrier frequency: selectable to 15 kHz
- 3% DC bus reactor: 30-150 HP, 208 VAC;
30-150 HP, 240 VAC;
- 40-500 HP, 480 VAC; optional on lower
ratings
- 24 VDC control logic, PNP / NPN selectable
- Transmitter/Option power supply
- input/output terminal status
- Timer function: Elapsed time, Delay on
start, Delay on stop
- RS-422/485 port: Modbus protocol
- Volts/hertz ratio: Preset and programmable
V/Hz patterns
- Meter Functions: Volt, amp, kilowatt,
elapsed run time, speed command
- NEMA 1 or protected chassis
- UL, cUL listed and CE marked; IEC 146;
- MTBF: exceeds 28 years
- DriveWizard upload/download and
monitoring/graphing software
Service Conditions
- Ambient Temperature:
-10 °C to 40 °C NEMA 1, 45 °C protected chassis
(14 °F to 104 °F, 113 °F)
- Humidity: 95% RH, non-condensing
- Altitude: 3300 ft; higher by derate
- Input voltage: +10%/-15%
- Input frequency: 50/60 Hz ± 5%
- 3-phase, 3-wire, phase sequence
insensitive
Bypass Features
- Input, output, and bypass contactors
- Circuit breaker disconnect (MCP)
- Thermal motor overload relay, class 20
- 115 VAC control transformer, fused
- Drive/Bypass selector
- Hand/Off/Auto selector
- Normal/Test selector
- Pilot lights
- Selectable auto transfer to bypass on
drive fault
- Run mode and Fault contacts
- Safety circuit interlock
- Control and safety circuit terminal strip
- Customer Use, 115 VAC, 100 VA
|
|
|
|
|
|
|
Rev Date |
Size |
|
EZZ006543 |
Making Yaskawa Inverter Products Conform with the
EMC Directive |
Technical Manuals |
4/4/2002 |
353 KB |
|
IG.AFD.12 |
Installation Guide for Profibus DP Option CM061 |
Installation Guides |
7/1/2004 |
1.1 MB |
|
IG.AFD.14 |
Installation Guide for DeviceNet Option Card CM05X
|
Installation Guides |
7/1/2004 |
109 KB |
|
IG.AFD.17 |
Installation Guide for Modbus Plus Option Card CM071
|
Installation Guides |
7/1/2004 |
1.8 MB |
|
IG.AFD.20 |
Installation Guide for LonWorks Option |
Installation Guides |
7/1/2004 |
94 KB |
|
IG.AFD.25 |
Installation Guide for EthernetModbusTCP/IP Option
CM090 |
Installation Guides |
7/1/2004 |
121 KB |
|
IG.AFD.50 |
Installation Guide for Pressure Transducer 3-15 PSI
Analog Input Option Card AI-010 |
Installation Guides |
7/1/2004 |
147 KB |
|
IG.AFD.62 |
Installation Guide for Analog Input Trim
Potentiometer Option Card AI-001 |
Installation Guides |
7/1/2004 |
31 KB |
|
IG.AFD.67 |
Installation Guide for 120VAC Interface Option Card
DI-002 |
Installation Guides |
10/3/2004 |
60 KB |
|
TM.AFD.12 |
Technical Manual for Profibus-DP Option CM052 |
Technical Manuals |
1/31/2004 |
2.4 MB |
|
TM.AFD.14 |
Technical Manual for DeviceNet Option CM05x |
Technical Manuals |
4/1/2004 |
523 KB |
|
TM.AFD.20 |
Technical Manual for LonWorks Option |
Technical Manuals |
3/30/2004 |
479 KB |
|
TM.DW.03 |
DriveWizard 6.0 Software User Manual |
Technical Manuals |
9/14/2004 |
1.6 MB |
|
TM.P7.01 |
P7 DRIVE USER MANUAL |
Technical Manuals |
11/1/2004 |
4.3 MB |
|
TM.P7.02 |
P7 Drive Programming Manual |
Technical Manuals |
11/1/2004 |
2.5 MB |
|
TM.P7.21 |
Technical Manual for P7 Apogee FLN |
Technical Manuals |
9/13/2004 |
3.0 MB |
|
TM.P7.22 |
Technical Manual for P7 Metasys N2 |
Technical Manuals |
9/13/2004 |
2.8 MB |
|
TM.P7B.01 |
P7B DRIVE BYPASS TECHNICAL MANUAL |
Technical Manuals |
10/1/2003 |
2.9 MB |
|
|
1/8 - 10 Horsepower General Purpose Vector
Drive

|
Specifications and Features for V7 Drive
|
The V7 Drive is a high performance AC drive for induction motors,
providing low motor noise and high starting torque. The V7 provides
two control methods; V/f and open loop vector control for precision
speed regulation applications. In addition to good speed regulation,
open loop vector control also provides higher torque at lower
speeds. The V7 is intended for constant torque applications, with
current overload rating of 150% for 60 seconds.
The V7 is fully featured and compact. The digital operator
provides 4-digit LED status display with a built-in analog speed
potentiometer, as well as digital programming of almost 200
parameters. The digital pulse train input provides a precise
frequency input, and is the perfect solution for speed / follower
applications. The seven standard multi-function inputs can be
programmed to allow for 17 preset speeds. The V7 also has an analog
input, a multi-function output, two multi-function open collector
outputs, and an analog output as standard.
The V7 is ideally suited for applications such as conveyors,
grinders, centrifuges, pumps, fans, blowers, machine tools,
packaging, food processing, and commercial laundry.
One of the outstanding options for the V7 is DriveWizard. This
software enables upload, download, and monitoring of parameters.
Another software, CASE, can add functionality to the drive by
reconfiguring drive defaults, establishing presets for OEM
equipment, and by eliminating peripheral controls and PLCs.
A RS-485 Modbus RTU communication port is standard, allowing 32
nodes on a single network. Plug-in interface option boards enable
the drive to communicate with all the major networks, such as
DeviceNet, Profibus-DP, and others. The option board installs
directly on the drive control board via simple snap-in connectors.
A version of this drive called V7N is available with DeviceNet
embedded in the drive control board, reducing cost and installation
time.
Another version of this drive called V74X is available with integral
NEMA 4X/12 enclosure for dusty and wet environments.
The V7 is provided in a NEMA 1 enclosure from 1/8 to 10 HP at 230
VAC and 1/2 to 10 HP at 460 VAC. (This V7 was previously named GPD
315/V7)
Performance Features
- Ratings:
1/8 to 10 HP at 230 VAC, 1/2 to 10 HP at 460 VAC
- Constant torque overload rating:
150% for 1 min., 200% for 30 Sec. (250% peak)
- DC injection braking, ramp to stop
- Electronic reversing
- Adjustable accel/decel: 0.01 to 6000
seconds
- Controlled speed range: (1)40:1,
(2)100:1
- Speed Regulation (1) ± 0.5 to 1%
with slip compensation (2)± 0.2%
- Drive efficiency: 95%
- Displacement power factor: 0.98
- Output frequency: .1 to 400 Hz
- Frequency resolution: 0.01 Hz with digital
reference, 0.06 / 60 Hz with analog reference
- Frequency accuracy: 0.01% with digital
command, 0.5% with analog command
- Volts / hertz ratio: infinitely adjustable
pattern
- Open loop vector control
- DC Injection braking: adjustable
amplitude, duration, current limited
- Torque boost: full range, auto
- Power loss ride-thru: 0.5 sec.
- Speed search
- Auto restart
- 3 Critical frequency rejection settings
- Slip Compensation
- Energy Savings Function
- PID with loss of feedback function
Protective Features
- Current limit, stall prevention during
accel, decel, and run
- Motor and drive overload
- Over voltage
- Instantaneous over current
- Short circuit
- Under voltage
- Heatsink overheat
- Ground fault protection
- Over/under torque
Control Methods:
(1) V/Hz Mode
(2) Open Loop Vector Mode
|
Design Features
- 16-bit microprocessor logic
- Digital keypad operator with analog speed
pot
- LED status display
- Copy Keypad Function
- Remote Mount Keypad Capability
- RJ45 Style Digital Operator Connector
- 7 multi-function digital inputs
- Programmable form C output contact for
customer use:
1A at 250 VAC or 30 VDC
- 24 VDC control logic compatible with
sourcing or sinking outputs (PNP or NPN)
- Carrier frequency: 10 kHz maximum
- 16 multi-speed settings plus jog speed
- Remote speed reference: 0-10 VDC (20 kohms)
or 4-20 mA (250 ohms)
- Signal follower: bias and gain
- 2 programmable open collector outputs
- Analog monitor output:
0-10 VDC proportional to output frequency or output
current
- Approximately 200 parameters
- Digital pulse train input (30 kHz max.)
- Cooling fan controlled by drive run/stop
- RS-485/RS-422 serial communication port
(up to 32 nodes)
- Baud rate of 19.2 kbps
- UL and cUL listed; CE approved
- UL recognized electronic overload
- MTBF: exceeds 28 years
- Dynamic Braking Transistor
- NEMA 1 enclosure
Service Conditions
- Ambient service temperature:
-10° to 40°C (14° to 105°F)
- Ambient storage temperature:
-20° to 60°C (-4° to 140°F)
- Humidity: to 95% non-condensing
- Altitude: to 3280 ft; higher by derating
- Service factor: 1.0
- Input voltage: -15% to +10%
200 to 230 VAC,
380 to 460 VAC
- Input frequency:+/-5%; 50/60 Hz
- Phase sequence insensitive
|
|
|
|
|
|
|
Rev Date |
Size |
|
2Y25-0514 |
Serial Communication Option Kit GPD315 V7 |
Installation Guides |
8/23/2001 |
1.8 MB |
|
2Y25-0516 |
Remote Digital Operator Kit, DS081 & DS083 for V7
Drive |
Installation Guides |
8/24/2001 |
293 KB |
|
2Y25-0518 |
Bi-Polar Analog Input Card, DS080 for V7 Drive |
Installation Guides |
8/23/2001 |
95 KB |
|
2Y25-0519 |
Auxiliary Analog Input Connector Assy. DS082 for V7
GPD315 |
Installation Guides |
7/16/2003 |
139 KB |
|
2Y25-0520 |
Remote Digital Operator Kit, DS084 & DS086 Nema 1
for V7 GPD315 |
Installation Guides |
8/28/2001 |
360 KB |
|
EZZ006543 |
Making Yaskawa Inverter Products Conform with the
EMC Directive |
Technical Manuals |
4/4/2002 |
353 KB |
|
IG.V7.01 |
Installation Guide for V7 and V74X |
Installation Guides |
8/1/2003 |
737 KB |
|
IG.V7.12 |
Installation Guide for V7 Profibus DP Option CM067 |
Installation Guides |
7/1/2004 |
137 KB |
|
IG.V7.13 |
Installation Guide for V7 DeviceNet Option CM052 |
Installation Guides |
7/1/2004 |
132 KB |
|
IG.V7.69 |
Installation Guide for 120VAC Interface Option Card
DI-004, DI-005 |
Installation Guides |
7/1/2004 |
235 KB |
|
TM.DW.03 |
DriveWizard 6.0 Software User Manual |
Technical Manuals |
9/14/2004 |
1.6 MB |
|
TM.V7.01 |
V7 and V74X DRIVES TECHNICAL MANUAL |
Technical Manuals |
8/1/2003 |
2.5 MB |
|
TM.V7.12 |
Technical Manual for V7 Profibus-Dp Option CM067 |
Technical Manuals |
6/20/2002 |
3.2 MB |
|
TM.V7SW.025 |
V7 High Carrier Frequency 14.5kHz Software Technical
Manual |
Technical Manuals |
7/1/2004 |
14 KB |
|
TM.V7SW.026H |
V7 High Frequency 800Hz Software Technical Manual
Version for 230V/460V class 5.5/7.5kW |
Technical Manuals |
7/1/2004 |
70 KB |
|
TM.V7SW.026L |
V7 High Frequency 800Hz Software Technical Manual
version for 230V/460V class 4.0kW or less |
Technical Manuals |
7/1/2004 |
70 KB |
|
TM.V7SW.028 |
V7 PID for Trim Control Software Technical Manual |
Technical Manuals |
7/1/2004 |
88 KB |
|
TM.V7SW.029 |
V7 Traverse Software Technical Manual |
Technical Manuals |
7/1/2004 |
59 KB |
|
TM.V7SW.030 |
V7 Decel Positioning Software Technical Manual |
Technical Manuals |
12/2/2004 |
46 KB |
|
TM.V7SW.031 |
V7 for Extended S-Curve Software Technical Manual |
Technical Manuals |
7/1/2004 |
8 KB |
|
TM.V7SW.032H |
V7 Textile Fiber Winder Software Technical Manual |
Technical Manuals |
7/1/2004 |
38 KB |
|
TM.V7SW.032L |
V7 Textile Fiber Winder Software Technical Manual |
Technical Manuals |
7/1/2004 |
34 KB |
|
TM.V7SW.034 |
V7 Enhanced Memobus Software Technical Manual |
Technical Manuals |
7/1/2004 |
18 KB |
|
TM.V7SW.037 |
V7 External Terminal DC Injection Software Technical
Manual |
Technical Manuals |
7/1/2004 |
25 KB |
|
TM.V7SW.039 |
V7 Enhanced PID Software Technical Manual |
Technical Manuals |
7/1/2004 |
147 KB |
|
TM.V7SW.041 |
V7 Limit Switch Software Technical Manual |
Technical Manuals |
7/1/2004 |
47 KB |
|
TM.V7SW.052 |
V7 Software DC Injection and Trim Control Technical
Manual |
Technical Manuals |
7/1/2004 |
72 KB |
|
TM.V7SW.054 |
V7 Software for 2 motor selection Technical Manual |
Technical Manuals |
7/1/2004 |
31 KB |
|
TM.V7SW.068 |
V7 Software for PID Trim Control Technical Manual |
Technical Manuals |
7/1/2004 |
65 KB |
|
TM.V7SW.070 |
Enhanced 18.8A Current Rating Model 47P5 Only |
Technical Manuals |
7/1/2004 |
17 KB |
|
TM4320 |
Technical Manual for V7 with DeviceNet Option |
Technical Manuals |
11/1/2001 |
1.9 MB |
|
TM4323 |
Technical Manual for V7 with Profibus II Option |
Technical Manuals |
7/12/2001 |
581 KB |
|
TM4325 |
Technical Manual for V7 with Modbus RTU Option |
Technical Manuals |
7/12/2001 |
701 KB |
|
YEA-TOA-S606-11A |
Instruction Manual VS-606V7 Series |
Technical Manuals |
12/1/1999 |
1.8 MB |
|
YEA-TOS-S606.11.A |
Serie VS mini V7 Manual de instrucciones |
Technical Manuals |
12/1/1999 |
| |