Seltrol is a stocking distributor of a wide variety of industrial automation equipment. We are located in South Carolina and service SC and NC. Our inside and outside sales staff are available to assist you with your application. We provide technical - application support for all of our products

Yaskawa / Magnetek AC Inverters and AC Vector Drives

 

F7 Drive
1/2 - 500 Horsepower Industrial Workhorse

 

Specifications and Features for F7 Drive

 

The F7 Drive: This AC drive is the Industrial Workhorse that can handle every conventional application found within the typical industrial plant, from simple variable torque pumping to sophisticated networked material handling. All of this is possible with the smart and flexible design platform of the F7, providing both Normal and Heavy Duty ratings, four modes of control, network communication options, application-specific drive software, and an array of standard and optional input/output choices.

The F7 is factory-programmed and ready to run. For operational simplicity and clarity, the LCD operator display has 5 lines x 16 characters. It can be set to any of 7 languages. The keypad is intuitive and includes parameter copying to move a chosen set of parameters from one drive to another. If the application requires programming, the F7 makes it easy. Parameters are grouped in easy to use sets; quick start and advanced. To enhance parameter and data management, DriveWizard software for the PC is available at no charge, for upload/download, trending, and graphing.

This drive is designed for tough industrial environments. It is rugged and reliable, with an MTBF of 28 years. A variety of enclosure options provide the right environmental protection. The dual ratings, Normal and Heavy duty, enable the most economical match of overload capacity and starting torque for the application. Providing the right fit to power requirements is also easy with 208/240 and 480 volt ratings, built-in bus choke above 30 HP, 12-pulse capability above 30 HP, common bus capability, and regeneration options. Patented high slip braking can eliminate the need for dynamic braking resistors for high inertia loads. Other features include motor auto-tuning and a wide range of configurable options, such as breakers and fuses.

To provide the optimum control method, the F7 can operate in conventional V/f, V/f with encoder feedback, open loop vector, or closed loop vector mode. Drive performance can be further enhanced for a specific application with optional software.

The F7 supports the industry’s open architecture, open connectivity demands with network communications choices such as DeviceNet, Profibus-DP, and others. Drive coordination with other equipment is simplified with inputs and outputs for digital pulse train, 4 to 20 mA, -10 to +10 V, and an assortment of programmable contacts.

For new installations or retrofits, the F7 is truly the Industrial Workhorse, perfect for every conventional application…and even some unconventional ones

 

 
Performance Features
  • Ratings:
    0.5 to 150 HP, 208 to 240 VAC
    0.75 to 500 HP, 480 VAC 
  • Overload capacity:
    150% for 1 min heavy duty, nominal 110% for 1 min normal duty
  • Starting torque:
    150%, at 1Hz (V/f), at 0.5 Hz (open loop), at 0.3 Hz (closed loop)
  • Output frequency: 
    0.01 to 300 Hz for heavy duty, 400 Hz for normal duty
  • Controlled speed range:
    40:1 (V/f), 50:1 (V/f with PG), 200:1 (open loop), 1000:1 (closed loop)
  • Speed regulation:
    2-3% (V/f), 0.02% (V/f with PG), 0.2% (open loop), 0.01% (closed loop)
  • Speed/frequency resolution:
    0.01% with digital reference, 0.1% with analog reference, 0.1 Hz with Modbus
  • Electronic reversing
  • Adjustable accel/decel: 0.1 to 6000 sec
  • Stall prevention
  • Drive efficiency: 96 to 98%
  • Displacement power factor: 0.98
  • Power loss ride-thru: 2 sec
  • Inertial ride-thru
  • Selectable auto restart after momentary power loss
  • Programmable auto restart
    (0 to 10 attempts) on re-settable fault
  • Critical frequency rejection: 3 selectable, adjustable bands


Protective Features

  • DC bus CHARGE indicator
  • Optically-Isolated controls
  • Phase-to-phase / phase-to-neutral short circuit protection
  • Ground fault protection
  • Electronic motor overload (UL)
  • Current and torque limit
  • Over-torque / under-torque detection
  • Fault circuit: over-current, over-voltage, and over-temperature
  • Input/output phase loss


Inputs and Outputs

  • Analog inputs:
    -10 to +10 VDC (20K ohms) or 4 to 20 mA (250 ohm)
  • Analog outputs:
    -10 to +10 VDC or 4-20 mA proportional to output parameters
  • Digital pulse train input/output (32 KHz max)
  • Digital Inputs: 8 multi-function
  • Programmable outputs: Three form A
  • Fault contacts: form C
  • RS-485/422 communication terminals
     

Additional Features for V/f

  • Torque boost: full range, auto
  • V/f ratio: 15 preset, one adjustable
  • Slip compensation
Design Features
  • LCD keypad display, 5 lines x 16 characters, backlit, 7 languages, copy function
  • Multi-speed settings: 17 available
  • Setpoint (PID) trim control
  • Signal follower: bias and gain
  • Up / down / hold reference (digital M.O.P.)
  • Timer function; on/off delay
  • 32-bit microprocessor logic
  • Easy access, quick start parameter groups
  • Nonvolatile memory/program retention
  • Flash memory for update and custom applications
  • 24 VDC control logic
  • DC injection braking, adjustable level
  • Dynamic braking
  • High-slip braking
  • Ramp to stop or coast to stop
  • Dual motor parameter sets
  • Synchronized start into rotating motor
  • Motor auto-tuning, static and dynamic
  • Common bus capability
  • DC link choke: 30 to 150 HP at 240 VAC, 30 to 500 HP at 480 VAC
  • Twelve-pulse capability: 30 to 150 HP at 240 VAC, 30 to 500 HP at 480 VAC
  • Terminal strip, quick disconnect
  • Split cover for easy wiring
  • Plug-in heat sink fan


Service Conditions

  • Ambient service temperatures:
    -10 to 40 0C (1040F) NEMA 1, to 450C (1130F) protected chassis
  • Humidity: non-condensing 95%
  • Altitude: to 3300 feet (1000 meter)
  • Input voltage: +10% / -15%, 3 phase
    200 to 240 VAC, 380 to 480 VAC
  • Enclosure: NEMA 1 or protected chassis (other options)
  • Input frequency: 50/60 Hz ± 5%
  • 3-phase, 3-wire phase insensitive
  • Vibration: 1G, (10 to 20Hz), 0.2G (20 to 50Hz)


Standards & Reliability

  • UL, cUL & CE listed
  • IEC: 146A
  • MBTF: Exceeds 28 years
  • Tested on fully-loaded motors
  • Surface mount technology

 

 

Documentation

Number
Title   
Type 
 
Rev Date Size
EZZ006543 Making Yaskawa Inverter Products Conform with the EMC Directive Technical Manuals 4/4/2002 353 KB
IG.AFD.12 Installation Guide for Profibus DP Option CM061 Installation Guides 7/1/2004 1.1 MB
IG.AFD.13 Installation Guide for DeviceNet Option Card CM059 Installation Guides 7/1/2004 124 KB
IG.AFD.14 Installation Guide for DeviceNet Option Card CM05X Installation Guides 7/1/2004 109 KB
IG.AFD.17 Installation Guide for Modbus Plus Option Card CM071 Installation Guides 7/1/2004 1.8 MB
IG.AFD.20 Installation Guide for LonWorks Option Installation Guides 7/1/2004 94 KB
IG.AFD.25 Installation Guide for EthernetModbusTCP/IP Option CM090 Installation Guides 7/1/2004 121 KB
IG.AFD.50 Installation Guide for Pressure Transducer 3-15 PSI Analog Input Option Card AI-010 Installation Guides 7/1/2004 147 KB
IG.AFD.51 Installation Guide for Analog Ouput Option Card AO-08 AO-12 Installation Guides 7/1/2004 63 KB
IG.AFD.52 Installation Guide for Isolated Analog Output Option Card AO-001 Installation Guides 11/3/2004 89 KB
IG.AFD.53 Installation Guide for Analog Input Option Card AI-14U Installation Guides 7/1/2004 44 KB
IG.AFD.54 Installation Guide for Analog Input Option Card AI-14B Installation Guides 7/1/2004 81 KB
IG.AFD.55 Installation Guide for Isolated Analog Input Option Card AI-040 Installation Guides 7/1/2004 80 KB
IG.AFD.56 Installation Guide for Digital Output Option Card DO-08 Installation Guides 7/1/2004 108 KB
IG.AFD.57 Installation Guide for Digital Output Option Card DO-02C Installation Guides 7/1/2004 113 KB
IG.AFD.58 Installation Guide for Digital Input Option Card DI-08 Installation Guides 7/1/2004 49 KB
IG.AFD.59 Installation Guide for Digital Input Option Card DI-16H2 Installation Guides 7/1/2004 68 KB
IG.AFD.60 Installation Guide for Encoder Feedback Option Card PG-X2 Installation Guides 7/1/2004 114 KB
IG.AFD.61 Installation Guide for Dual Encoder Feedback Option Card PG-W2 Installation Guides 7/1/2004 101 KB
IG.AFD.62 Installation Guide for Analog Input Trim Potentiometer Option Card AI-001 Installation Guides 7/1/2004 31 KB
IG.AFD.63 Installation Guide for 120 VAC Interface Option Card DI-001 Installation Guides 10/3/2004 63 KB
IG.F7C.01 Installation Guide for Heatsink Filter Kit Option for F7 Configured Drive Installation Guides 3/5/2004 87 KB
TM.AFD.12 Technical Manual for Profibus-DP Option CM052 Technical Manuals 1/31/2004 2.4 MB
TM.AFD.13 Technical Manual for DeviceNet Option CM059 Technical Manuals 5/1/2004 929 KB
TM.AFD.14 Technical Manual for DeviceNet Option CM05x Technical Manuals 4/1/2004 523 KB
TM.AFD.20 Technical Manual for LonWorks Option Technical Manuals 3/30/2004 479 KB
TM.DW.03 DriveWizard 6.0 Software User Manual Technical Manuals 9/14/2004 1.6 MB
TM.F7.01 F7 DRIVE USER MANUAL Technical Manuals 10/15/2004 3.9 MB
TM.F7.02 F7 Drive Programming Manual Technical Manuals 11/1/2004 1.7 MB
TM.F7.11 Technical Manual for F7 Parameter Access Technical Manuals 2/1/2004 2.1 MB
TM.F7SW.056 F7 Drive Software Technical Manual 1500 Hz Output Frequency Technical Manuals 7/1/2004 1.3 MB
TM.F7SW.064 F7 Drive Software Technical Manual Electronic Lineshaft Technical Manuals 7/1/2004 1.4 MB
TM.F7SW.076 F7 Drive Software Technical Manual Differential PID for Gas Well Technical Manuals 7/14/2004 49 KB
YEA-TOE-S616-55.1 Instruction Manual Varispeed-F7 Spec A Technical Manuals 3/1/2001 6.8 MB
YEA-TOE-S616-55.3 Instruction Manual Varispeed-F7 Obsolete manual for F7U Technical Manuals 10/1/2001 6.2 MB

 

G7 Drive
1/2 - 500 Horsepower The Ultimate Drive Solution

Specifications and Features for G7 Drive

 

This amazing AC drive is the ultimate performance solution with increased speed and torque response to provide servo-like performance from an induction motor. In addition, the
G7 drive includes the world’s first Inverter architecture that eliminates or minimizes the installation problems associated with IGBT switching on 480 volt systems and protects the entire motor-drive system.

G7 drive performance makes it the ideal drive for high performance speed, torque, or position control applications. Several control modes are provided. In open loop vector mode, the latest flux observer algorithms extend speed range and provide maximum starting torque. In closed loop vector mode, 0.01% speed regulation and 1000:1 control range can be achieved. Zero-servo capability provides position control at zero speed.

The G7 drive has the world’s first 480V 3-Level Inverter architecture for total system protection. This patented 3-Level architecture can eliminate peripheral components typically required to solve installation problems sometimes encountered on 480 volt systems. The G7 allows motor operation at very long cable lengths, meeting NEMA MG1 Part 31, with peak voltage being 30% less than conventional. With motor bearing current being typically 50% less than standard inverters, the G7 provides four times the motor bearing life. Audible motor noise on the 480 volt G7 drive is 5-10 dB (20%) less than the prior generation drive, even when operating at half the carrier frequency. Common mode current is half that of conventional drives. The G7 power section includes built-in bus choke (most ratings), 12-pulse input capability (most ratings), common DC bus capability, and regeneration options.

The G7 drive has three autotuning methods to optimize motor control, including the new static autotuning which does not require load decoupling nor motor rotation. The LCD operator displays 5 lines x 16 characters, in any of 7 languages. The keypad is intuitive and includes memory for parameter settings, making it easy to transfer settings from one drive to another. To further aid in parameter management, DriveWizard™ software for the PC is available at no charge, for upload, download, archiving, trending, and graphing.

The G7 drive has a large programming feature set to handle sophisticated industrial applications. If the standard feature set does not meet your specific requirement, the G7 can be programmed using DriveWorksEZ™. This is a PC-based, object-oriented, graphical icon programming tool that is friendly to the user. The drive firmware can also be modified by custom or prewritten application-specific modules such as
Motion Control or Electronic Lineshaft.

The G7 drive supports the industry’s preference for open network architecture and connectivity with network choices such as DeviceNet, Profibus-DP, Ethernet, and others.
 
The G7 is not intended for the simple, routine AC drive application, it is for the challenges. The G7 drive offers the ultimate performance, the best system protection, and the most flexible configurations of any drive available.

 

 
Performance Features
  • Ratings: 0.5 to 150 HP, 240 VAC
    0.5 to 500 HP, 480 VAC
  • Overload capacity: Heavy duty, 150% for 1 minute, 200% peak
  • Starting torque: 150% at frequency;
    1.0Hz (V/f), 0.5Hz (open loop vector), 0.0Hz (closed loop vector)
  • Output frequency: 0.01 to 400 Hz
  • Output frequency resolution: 0.001 Hz
  • Speed control range:
    40:1 (V/f), 200:1 (open loop vector), 1000:1 (closed loop vector)
  • Speed regulation:
    1.0% (V/f), 0.2% (open loop vector),
    0.01% (closed loop vector)
  • Speed response: 60 Hz
  • Torque response: 300 Hz
  • Speed reference resolution:
    0.01 Hz with digital reference,
    0.03 Hz with analog reference,
    0.01 Hz with network reference
  • Speed/Torque/Position control
  • Zero-servo mode
  • Adjustable accel/decel: 0.01 to 6000 seconds
  • S-Curve: 0.00 to 2.50 seconds, adjustable for each corner
  • Stall prevention: Accel / decel / running
  • Power loss ride-thru: Auto-restart or inertia ride-thru


Protective Features

  • Torque limit (four quadrant)
  • Electronic motor overload (UL 508C)
  • Over-torque / under-torque detection
  • Phase-to-phase and ground fault short circuit protection
  • Over-current, over-voltage, and overtemperature protection
  • Input / output phase loss protection
  • Optically-isolated controls
  • DC bus charge indicator
  • Motor thermistor input


Inputs and Outputs

  • Analog inputs: 3 (2 programmable), -10 to
    +10 VDC (20k) or 4 to 20 mA (250), 11 bit plus sign
  • Analog outputs: 2 programmable, -10 to
    +10 VDC or 4-20 mA, 9 bit plus sign
  • Digital inputs: 12 (10 programmable), sinking or sourcing
  • Digital outputs: 5 programmable, 3 form A and 2 open collector
  • Pulse train input: 1 programmable, 32 kHz max
  • Pulse train output: 1 programmable, 32 kHz max
  • Fault contact: 1 form C
  • RS-232/422/485: Modbus RTU


Standards & Reliability

  • UL, cUL, and CE listed
  • MTBF: Exceeds 28 years
Design Features
  • LCD keypad display: 5 lines x 16 characters, backlit, 7 languages, copy function
  • Simple programming: Quick start and modified parameter groups
  • Microprocessor logic: 32-bit
  • Memory type: Flash memory for easy updates, custom software applications, and non-volatile program retention
  • Control logic: 24 VDC (sinking or sourcing)
  • Terminal strip: Quick disconnect
  • Front cover: Split for easy wiring
  • Heat sink fan: Plug-in with on-off control
  • Motor auto-tuning: Static and rotational
  • Speed search: Bi-directional into rotating motor
  • Process control: PID, reference with PID trim
  • Motor parameters: 2 sets
  • Stopping methods: Ramp stop, coast stop, fast stop, or high-slip braking
  • DC injection braking: Adjustable level and time
  • Speed reference presets: 17 available
  • Timer function: Programmable on / off delay
  • Digital M.O.P.: Up / down / hold / reset reference
  • Bias and gain: All analog and pulse train I/O
  • Common DC bus capability: All models
  • Dynamic braking transistor: 20 HP and below (240 VAC), 25 HP and below (480 VAC)
  • DC bus choke: 25 HP and above (240 VAC) 30 HP and above (480 VAC)
  • Twelve-pulse capability: 25 HP and above (240 VAC), 30 HP and above (480 VAC)


Service Conditions

  • Enclosure: NEMA 1 or protected chassis
  • Ambient service temperatures:
    -10 to 40 0C (104 0F) NEMA 1,
    -10 to 45 0C (113 0F) protected chassis
  • Input frequency: 50 / 60 Hz ± 5%
  • Input voltage: +10% / -15%, 3 phase, 240 or 480 VAC, phase insensitive
  • Humidity: Non-condensing, 95% maximum
  • Altitude: 3300 feet (1000 meters) w/o derate
  • Vibration: 1G (10 to 20 Hz), 0.6G or less (20 to 55 Hz)


Three-Level 480V Inverter Benefits

  • Lead length: Meets NEMA MG1 Part 31
  • Four times the motor bearing life
  • Quiet operation: 5-10 dB of noise reduction
  • Common mode current: 50% reduction

 

 

Number
Title   
Type 
 
Rev Date Size
EZZ006543 Making Yaskawa Inverter Products Conform with the EMC Directive Technical Manuals 4/4/2002 353 KB
IG.AFD.12 Installation Guide for Profibus DP Option CM061 Installation Guides 7/1/2004 1.1 MB
IG.AFD.13 Installation Guide for DeviceNet Option Card CM059 Installation Guides 7/1/2004 124 KB
IG.AFD.14 Installation Guide for DeviceNet Option Card CM05X Installation Guides 7/1/2004 109 KB
IG.AFD.17 Installation Guide for Modbus Plus Option Card CM071 Installation Guides 7/1/2004 1.8 MB
IG.AFD.20 Installation Guide for LonWorks Option Installation Guides 7/1/2004 94 KB
IG.AFD.25 Installation Guide for EthernetModbusTCP/IP Option CM090 Installation Guides 7/1/2004 121 KB
IG.AFD.50 Installation Guide for Pressure Transducer 3-15 PSI Analog Input Option Card AI-010 Installation Guides 7/1/2004 147 KB
IG.AFD.51 Installation Guide for Analog Ouput Option Card AO-08 AO-12 Installation Guides 7/1/2004 63 KB
IG.AFD.52 Installation Guide for Isolated Analog Output Option Card AO-001 Installation Guides 11/3/2004 89 KB
IG.AFD.53 Installation Guide for Analog Input Option Card AI-14U Installation Guides 7/1/2004 44 KB
IG.AFD.54 Installation Guide for Analog Input Option Card AI-14B Installation Guides 7/1/2004 81 KB
IG.AFD.55 Installation Guide for Isolated Analog Input Option Card AI-040 Installation Guides 7/1/2004 80 KB
IG.AFD.56 Installation Guide for Digital Output Option Card DO-08 Installation Guides 7/1/2004 108 KB
IG.AFD.57 Installation Guide for Digital Output Option Card DO-02C Installation Guides 7/1/2004 113 KB
IG.AFD.58 Installation Guide for Digital Input Option Card DI-08 Installation Guides 7/1/2004 49 KB
IG.AFD.59 Installation Guide for Digital Input Option Card DI-16H2 Installation Guides 7/1/2004 68 KB
IG.AFD.60 Installation Guide for Encoder Feedback Option Card PG-X2 Installation Guides 7/1/2004 114 KB
IG.AFD.61 Installation Guide for Dual Encoder Feedback Option Card PG-W2 Installation Guides 7/1/2004 101 KB
IG.AFD.62 Installation Guide for Analog Input Trim Potentiometer Option Card AI-001 Installation Guides 7/1/2004 31 KB
IG.AFD.63 Installation Guide for 120 VAC Interface Option Card DI-001 Installation Guides 10/3/2004 63 KB
IG.G7.68 Installation Guide for 120VAC Interface Option Card DI-003 Installation Guides 10/3/2004 118 KB
TM.AFD.12 Technical Manual for Profibus-DP Option CM052 Technical Manuals 1/31/2004 2.4 MB
TM.AFD.13 Technical Manual for DeviceNet Option CM059 Technical Manuals 5/1/2004 929 KB
TM.AFD.14 Technical Manual for DeviceNet Option CM05x Technical Manuals 4/1/2004 523 KB
TM.AFD.20 Technical Manual for LonWorks Option Technical Manuals 3/30/2004 479 KB
TM.DW.03 DriveWizard 6.0 Software User Manual Technical Manuals 9/14/2004 1.6 MB
TM.G7.01 G7 DRIVE TECHNICAL MANUAL Technical Manuals 9/1/2004 4.5 MB

 

P7 Drive
5 - 500 Horsepower Industrial Fan and Pump Drive

Specifications and Features for P7 Drive

 

For industrial applications such as centrifugal fans and pumps, the P7 drive is an ideal choice. The drive is provided in Normal Duty ratings with 110% overload capability. V/f control mode, network communication options, and an array of input/output options are available.

The P7 is factory-programmed and ready to run. For operational simplicity and clarity, the LCD operator display has 5 lines x 16 characters. It can be set to any of 7 languages. The keypad is intuitive and includes parameter copying to move a chosen set of parameters from one drive to another. If the application requires programming, the P7 makes it easy. Parameters are grouped in easy to use sets; quick start and advanced. To enhance parameter and data management, DriveWizard software for the PC is available at no charge, for upload/download, trending, and graphing.

This drive is designed for tough industrial environments. It is rugged and reliable, with an MTBF of 28 years. A variety of enclosure options provide the right environmental protection. Providing the right power requirements is also easy with 208/240 and 480 volt ratings, built-in bus choke above 30 HP, common bus capability, and other energy savings options. Other features include motor auto-tuning and configurable options such as circuit breakers and fuses.

The P7 supports the industry's open architecture, open connectivity demands with network communications choices such as DeviceNet, Profibus-DP, and others. Drive coordination with other equipment is simplified with inputs and outputs for 4 to 20 mA, 0-10 V, and an assortment of programmable contacts.

With an optional phase-shifting input transformer, the P7 dual-diode bridge can be operated in 12-pulse rectification mode, reducing input current harmonic distortion factor by over 90%. With lower EMI/RFI emission and lower total harmonic distortion contribution, the P7 meets or exceeds the generally accepted power quality standards. Inherent motor protection features resulting from low noise/low carrier technology provides for longer lead lengths without additional motor protection devices.

The optional P7/Bypass package is a 3-contactor style bypass, allowing motor operation from the drive or across the line. This facilitates drive maintenance while the motor continues to operate.

The P7 has been designed to provide the features and options commonly needed for fan and pump applications.


 

 
Performance Features
  • Ratings:
    5-150 HP, 208 VAC
    5-150 HP, 230 / 240 VAC
    5-500 HP, 480 VAC
    5-250 HP, Bypass
  • Overload capacity: nominal 110% for 60 sec (150% peak)
  • Starting torque: 100% at 3 Hz
  • DC injection braking: at start or stop, adjustable,
  • current-limited (anti-windmilling)
  • Motor preheat function
  • Adjustable accel/decel: 0.1 to 6000 sec.
  • Controlled speed range: 40:1
  • Critical frequency rejection: 3 selectable, adjustable bands
  • Torque-limiting: 30-180%
  • Energy $aving control
  • Torque boost: full range, auto
  • Power loss ride-thru: 2 sec
  • Inertia ride-thru
  • Auto restart after power loss or resettable fault, selectable,
  • programmable
  • Feedback signal loss detection
  • Serial communications loss detection
  • "Up/Down" floating point control capability
  • Stationary motor auto-tuning
  • Sleep function
  • Run-permissive input


Protective Features

  • Current-limited stall prevention
  • Heat sink over-temperature, speed fold-back
  • Bi-directional start into rotating motor
  • Current-limiting DC bus fuse
  • Optically-Isolated controls
  • Short circuit protection: Phase-phase and phase-neutral
  • Ground fault protection
  • Short circuit withstand rating: 65K RMS, 100K RMS with bus reactor
  • Electronic motor overload: UL
  • Current limit
  • Fault display: last 10 faults
  • Fault circuit: OC, OV, OT
  • Over torque and under torque protection
  • Reverse prohibit selectability


Inputs and Outputs

  • Output contacts: One form C and two programmable form A
  • Input terminals: 5 programmable multi-function input terminals
  • Fault input:  Programmable
  • Remote speed command: 0-10 VDC or 4-20 mA, direct or reverse-acting
  • Analog outputs: Programmable, two, 0-10 VDC
Design Features
  • LCD keypad display, 5 lines x 16 characters, backlit, 7 languages,
  • copy function
  • Multi-step speed settings: 5 available
  • Setpoint (PI) control
  • 32-bit microprocessor logic
  • Nonvolatile memory, program retention
  • Displacement power factor: 0.98
  • Output frequency: 0.1 to 120 Hz
  • Frequency resolution: 0.06 Hz
  • Frequency regulation: 0.1%
  • Control Terminal Board: Quick disconnect
  • Carrier frequency: selectable to 15 kHz
  • 3% DC bus reactor: 30-150 HP, 208 VAC; 30-150 HP, 240 VAC;
  • 40-500 HP, 480 VAC; optional on lower ratings
  • 24 VDC control logic, PNP / NPN selectable
  • Transmitter/Option power supply
  • input/output terminal status
  • Timer function: Elapsed time, Delay on start, Delay on stop
  • RS-422/485 port: Modbus protocol
  • Volts/hertz ratio: Preset and programmable V/Hz patterns
  • Meter Functions: Volt, amp, kilowatt, elapsed run time, speed command
  • NEMA 1 or protected chassis
  • UL, cUL listed and CE marked; IEC 146;
  • MTBF: exceeds 28 years
  • DriveWizard upload/download and monitoring/graphing software


Service Conditions

  • Ambient Temperature:
    -10 °C to 40 °C NEMA 1, 45 °C protected chassis
    (14 °F to 104 °F, 113 °F)
  • Humidity: 95% RH, non-condensing
  • Altitude: 3300 ft; higher by derate
  • Input voltage: +10%/-15%
  • Input frequency: 50/60 Hz ± 5%
  • 3-phase, 3-wire, phase sequence insensitive


Bypass Features

  • Input, output, and bypass contactors
  • Circuit breaker disconnect (MCP)
  • Thermal motor overload relay, class 20
  • 115 VAC control transformer, fused
  • Drive/Bypass selector
  • Hand/Off/Auto selector
  • Normal/Test selector
  • Pilot lights
  • Selectable auto transfer to bypass on drive fault
  • Run mode and Fault contacts
  • Safety circuit interlock
  • Control and safety circuit terminal strip
  • Customer Use, 115 VAC, 100 VA

 

 

Number
Title   
Type 
 
Rev Date Size
EZZ006543 Making Yaskawa Inverter Products Conform with the EMC Directive Technical Manuals 4/4/2002 353 KB
IG.AFD.12 Installation Guide for Profibus DP Option CM061 Installation Guides 7/1/2004 1.1 MB
IG.AFD.14 Installation Guide for DeviceNet Option Card CM05X Installation Guides 7/1/2004 109 KB
IG.AFD.17 Installation Guide for Modbus Plus Option Card CM071 Installation Guides 7/1/2004 1.8 MB
IG.AFD.20 Installation Guide for LonWorks Option Installation Guides 7/1/2004 94 KB
IG.AFD.25 Installation Guide for EthernetModbusTCP/IP Option CM090 Installation Guides 7/1/2004 121 KB
IG.AFD.50 Installation Guide for Pressure Transducer 3-15 PSI Analog Input Option Card AI-010 Installation Guides 7/1/2004 147 KB
IG.AFD.62 Installation Guide for Analog Input Trim Potentiometer Option Card AI-001 Installation Guides 7/1/2004 31 KB
IG.AFD.67 Installation Guide for 120VAC Interface Option Card DI-002 Installation Guides 10/3/2004 60 KB
TM.AFD.12 Technical Manual for Profibus-DP Option CM052 Technical Manuals 1/31/2004 2.4 MB
TM.AFD.14 Technical Manual for DeviceNet Option CM05x Technical Manuals 4/1/2004 523 KB
TM.AFD.20 Technical Manual for LonWorks Option Technical Manuals 3/30/2004 479 KB
TM.DW.03 DriveWizard 6.0 Software User Manual Technical Manuals 9/14/2004 1.6 MB
TM.P7.01 P7 DRIVE USER MANUAL Technical Manuals 11/1/2004 4.3 MB
TM.P7.02 P7 Drive Programming Manual Technical Manuals 11/1/2004 2.5 MB
TM.P7.21 Technical Manual for P7 Apogee FLN Technical Manuals 9/13/2004 3.0 MB
TM.P7.22 Technical Manual for P7 Metasys N2 Technical Manuals 9/13/2004 2.8 MB
TM.P7B.01 P7B DRIVE BYPASS TECHNICAL MANUAL Technical Manuals 10/1/2003 2.9 MB

 

V7 Drive
1/8 - 10 Horsepower General Purpose Vector Drive

Specifications and Features for V7 Drive

 

The V7 Drive is a high performance AC drive for induction motors, providing low motor noise and high starting torque. The V7 provides two control methods; V/f and open loop vector control for precision speed regulation applications. In addition to good speed regulation, open loop vector control also provides higher torque at lower speeds. The V7 is intended for constant torque applications, with current overload rating of 150% for 60 seconds.

The V7 is fully featured and compact. The digital operator provides 4-digit LED status display with a built-in analog speed potentiometer, as well as digital programming of almost 200 parameters. The digital pulse train input provides a precise frequency input, and is the perfect solution for speed / follower applications. The seven standard multi-function inputs can be programmed to allow for 17 preset speeds. The V7 also has an analog input, a multi-function output, two multi-function open collector outputs, and an analog output as standard.

The V7 is ideally suited for applications such as conveyors, grinders, centrifuges, pumps, fans, blowers, machine tools, packaging, food processing, and commercial laundry.

One of the outstanding options for the V7 is DriveWizard. This software enables upload, download, and monitoring of parameters. Another software, CASE, can add functionality to the drive by reconfiguring drive defaults, establishing presets for OEM equipment, and by eliminating peripheral controls and PLCs.

A RS-485 Modbus RTU communication port is standard, allowing 32 nodes on a single network. Plug-in interface option boards enable the drive to communicate with all the major networks, such as DeviceNet, Profibus-DP, and others. The option board installs directly on the drive control board via simple snap-in connectors.

A version of this drive called V7N is available with DeviceNet embedded in the drive control board, reducing cost and installation time.

Another version of this drive called V74X is available with integral NEMA 4X/12 enclosure for dusty and wet environments.

The V7 is provided in a NEMA 1 enclosure from 1/8 to 10 HP at 230 VAC and 1/2 to 10 HP at 460 VAC. (This V7 was previously named GPD 315/V7)

 

 
Performance Features
  • Ratings:
    1/8 to 10 HP at 230 VAC, 1/2 to 10 HP at 460 VAC
  • Constant torque overload rating:
    150% for 1 min., 200% for 30 Sec. (250% peak)
  • DC injection braking, ramp to stop
  • Electronic reversing
  • Adjustable accel/decel: 0.01 to 6000 seconds
  • Controlled speed range: (1)40:1, (2)100:1
  • Speed Regulation (1) ± 0.5 to 1% with slip compensation (2)± 0.2%
  • Drive efficiency: 95%
  • Displacement power factor: 0.98
  • Output frequency: .1 to 400 Hz
  • Frequency resolution: 0.01 Hz with digital reference, 0.06 / 60 Hz with analog reference
  • Frequency accuracy: 0.01% with digital command, 0.5% with analog command
  • Volts / hertz ratio: infinitely adjustable pattern
  • Open loop vector control
  • DC Injection braking: adjustable amplitude, duration, current limited
  • Torque boost: full range, auto
  • Power loss ride-thru: 0.5 sec.
  • Speed search
  • Auto restart
  • 3 Critical frequency rejection settings
  • Slip Compensation
  • Energy Savings Function
  • PID with loss of feedback function


Protective Features

  • Current limit, stall prevention during accel, decel, and run
  • Motor and drive overload
  • Over voltage
  • Instantaneous over current
  • Short circuit
  • Under voltage
  • Heatsink overheat
  • Ground fault protection
  • Over/under torque



Control Methods:
(1) V/Hz Mode
(2) Open Loop Vector Mode

Design Features
  • 16-bit microprocessor logic
  • Digital keypad operator with analog speed pot
  • LED status display
  • Copy Keypad Function
  • Remote Mount Keypad Capability
  • RJ45 Style Digital Operator Connector
  • 7 multi-function digital inputs
  • Programmable form C output contact for customer use:
    1A at 250 VAC or 30 VDC
  • 24 VDC control logic compatible with sourcing or sinking outputs (PNP or NPN)
  • Carrier frequency: 10 kHz maximum
  • 16 multi-speed settings plus jog speed
  • Remote speed reference: 0-10 VDC (20 kohms) or 4-20 mA (250 ohms)
  • Signal follower: bias and gain
  • 2 programmable open collector outputs
  • Analog monitor output:
    0-10 VDC proportional to output frequency or output current
  • Approximately 200 parameters
  • Digital pulse train input (30 kHz max.)
  • Cooling fan controlled by drive run/stop
  • RS-485/RS-422 serial communication port (up to 32 nodes)
  • Baud rate of 19.2 kbps
  • UL and cUL listed; CE approved
  • UL recognized electronic overload
  • MTBF: exceeds 28 years
  • Dynamic Braking Transistor
  • NEMA 1 enclosure


Service Conditions

  • Ambient service temperature:
    -10° to 40°C (14° to 105°F)
  • Ambient storage temperature:
    -20° to 60°C (-4° to 140°F)
  • Humidity: to 95% non-condensing
  • Altitude: to 3280 ft; higher by derating
  • Service factor: 1.0
  • Input voltage: -15% to +10%
    200 to 230 VAC,
    380 to 460 VAC
  • Input frequency:+/-5%; 50/60 Hz
  • Phase sequence insensitive

 

 

Number
Title   
Type 
 
Rev Date Size
2Y25-0514 Serial Communication Option Kit GPD315 V7 Installation Guides 8/23/2001 1.8 MB
2Y25-0516 Remote Digital Operator Kit, DS081 & DS083 for V7 Drive Installation Guides 8/24/2001 293 KB
2Y25-0518 Bi-Polar Analog Input Card, DS080 for V7 Drive Installation Guides 8/23/2001 95 KB
2Y25-0519 Auxiliary Analog Input Connector Assy. DS082 for V7 GPD315 Installation Guides 7/16/2003 139 KB
2Y25-0520 Remote Digital Operator Kit, DS084 & DS086 Nema 1 for V7 GPD315 Installation Guides 8/28/2001 360 KB
EZZ006543 Making Yaskawa Inverter Products Conform with the EMC Directive Technical Manuals 4/4/2002 353 KB
IG.V7.01 Installation Guide for V7 and V74X Installation Guides 8/1/2003 737 KB
IG.V7.12 Installation Guide for V7 Profibus DP Option CM067 Installation Guides 7/1/2004 137 KB
IG.V7.13 Installation Guide for V7 DeviceNet Option CM052 Installation Guides 7/1/2004 132 KB
IG.V7.69 Installation Guide for 120VAC Interface Option Card DI-004, DI-005 Installation Guides 7/1/2004 235 KB
TM.DW.03 DriveWizard 6.0 Software User Manual Technical Manuals 9/14/2004 1.6 MB
TM.V7.01 V7 and V74X DRIVES TECHNICAL MANUAL Technical Manuals 8/1/2003 2.5 MB
TM.V7.12 Technical Manual for V7 Profibus-Dp Option CM067 Technical Manuals 6/20/2002 3.2 MB
TM.V7SW.025 V7 High Carrier Frequency 14.5kHz Software Technical Manual Technical Manuals 7/1/2004 14 KB
TM.V7SW.026H V7 High Frequency 800Hz Software Technical Manual Version for 230V/460V class 5.5/7.5kW Technical Manuals 7/1/2004 70 KB
TM.V7SW.026L V7 High Frequency 800Hz Software Technical Manual version for 230V/460V class 4.0kW or less Technical Manuals 7/1/2004 70 KB
TM.V7SW.028 V7 PID for Trim Control Software Technical Manual Technical Manuals 7/1/2004 88 KB
TM.V7SW.029 V7 Traverse Software Technical Manual Technical Manuals 7/1/2004 59 KB
TM.V7SW.030 V7 Decel Positioning Software Technical Manual Technical Manuals 12/2/2004 46 KB
TM.V7SW.031 V7 for Extended S-Curve Software Technical Manual Technical Manuals 7/1/2004 8 KB
TM.V7SW.032H V7 Textile Fiber Winder Software Technical Manual Technical Manuals 7/1/2004 38 KB
TM.V7SW.032L V7 Textile Fiber Winder Software Technical Manual Technical Manuals 7/1/2004 34 KB
TM.V7SW.034 V7 Enhanced Memobus Software Technical Manual Technical Manuals 7/1/2004 18 KB
TM.V7SW.037 V7 External Terminal DC Injection Software Technical Manual Technical Manuals 7/1/2004 25 KB
TM.V7SW.039 V7 Enhanced PID Software Technical Manual Technical Manuals 7/1/2004 147 KB
TM.V7SW.041 V7 Limit Switch Software Technical Manual Technical Manuals 7/1/2004 47 KB
TM.V7SW.052 V7 Software DC Injection and Trim Control Technical Manual Technical Manuals 7/1/2004 72 KB
TM.V7SW.054 V7 Software for 2 motor selection Technical Manual Technical Manuals 7/1/2004 31 KB
TM.V7SW.068 V7 Software for PID Trim Control Technical Manual Technical Manuals 7/1/2004 65 KB
TM.V7SW.070 Enhanced 18.8A Current Rating Model 47P5 Only Technical Manuals 7/1/2004 17 KB
TM4320 Technical Manual for V7 with DeviceNet Option Technical Manuals 11/1/2001 1.9 MB
TM4323 Technical Manual for V7 with Profibus II Option Technical Manuals 7/12/2001 581 KB
TM4325 Technical Manual for V7 with Modbus RTU Option Technical Manuals 7/12/2001 701 KB
YEA-TOA-S606-11A Instruction Manual VS-606V7 Series Technical Manuals 12/1/1999 1.8 MB
YEA-TOS-S606.11.A Serie VS mini V7 Manual de instrucciones Technical Manuals 12/1/1999